Environment Monitoring System IP Temp CAT5 Video Extender HDMI VGA DVI KVM Switch, Video Splitter, Video Matrix Switch

Environment Monitoring System Rope-Style Leak Detection Sensors

Liquid, Water & Chemical Detection Sensors compatible with ENVIROMUX-2D, ENVIROMUX-5D and ENVIROMUX-16D

Rope-Style Leak Detection Sensors

Low-Cost Liquid Detection Sensor, Rope-Style


ENVIROMUX-LD-LCx-y
  • For detecting water presence and warning of flooding.
  • 100% waterproof electronics.
  • Detects any conductive liquid or moisture.
    • Water sensor cable cannot be in contact with any conductive surfaces or overlap on itself.
  • Minimum puddle: 0.06" (1.5 mm) diameter.
  • Voltage and current:
    • Open Circuit: 5VDC max @ 1µA.
    • Closed circuit: <300mV @ 10.7mA.
  • Available water sensor cable (x) lengths: 1/10/50/100/200/400/600 feet.
    • Material: PVC twisted pair with stainless 316 elements
    • Diameter: 0.14" (3.5 mm)
  • Available 2-wire cable (y) lengths: 5/10/20/50/100 feet.
    • Contact an NTI product consultant for cable lengths over 100 feet (30 meters) - supports up to 1,000 feet (305 meters).


Liquid Detection Sensor, Plenum Rope-Style


ENVIROMUX-LDx-y
  • For detecting water presence and warning of flooding.
  • 100% waterproof electronics.
  • Detects any conductive liquid or moisture.
  • Minimum puddle: 0.6" (15 mm) diameter.
  • Detects liquid depth >0.1" (2.5 mm).
  • Voltage and current:
    • Open Circuit: 5VDC max @ 1µA.
    • Closed circuit: <300mV @ 10.7mA.
  • Available water sensor cable (x) lengths: 1/10/50/100/200/400/600/800/1000 feet.
    • Bend radius: 0.375" (9.53 mm)
    • Operating temperature: 32 to 167°F (0 to 75°C).
  • Available 2-wire plenum cable (y) lengths: 5/10/20/50/100 feet.
    • Plenum rating: CL2P (UL)
    • Diameter: 0.25 in (6.35mm)
    • Contact an NTI product consultant for cable lengths over 100 feet (30 meters) - supports up to 1,000 feet (305 meters).
  • Regulatory approvals: CE, RoHS
  • Use self-adhesive clips (ENVIROMUX-CLPxx-LD) to prevent sensor rope cable from shifting after installation


Chemical Detection Sensor


ENVIROMUX-CDx-y
  • For detecting the presence of chemical liquid.
    • Reliably senses acids, bases, and other conductive liquids.
  • Detects liquid depth >0.1" (2.5 mm).
  • Minimum puddle: 0.6" (15 mm) diameter.
  • Chemical resistant – cable functions normally after seven-day exposure to:
    • Fresh deionized water
    • Tap water
    • Sulfuric acid (98%)
    • Sulfuric acid (50%)
    • Hydrochloric acid (37%)
    • Sodium hydroxide (10%)
    • Aqua regia
    • Ethylene glycol (60% in DI water)
  • Voltage and current:
    • Open Circuit: 5VDC max @ 1µA.
    • Closed circuit: <300mV @ 10.7mA.
  • Available chemical sensor cable (x) lengths: 1/10/50/100 feet.
    • 100% waterproof
  • Available 2-wire cable (y) lengths: 5/10/20/50/100 feet.
    • Contact an NTI product consultant for cable lengths over 100 feet (30 meters) – supports up to 1,000 feet (305 meters).
  • Use self-adhesive clips (ENVIROMUX-CLPxx-LD) to prevent sensor rope cable from shifing after installation


Legacy Liquid Detection Rope Sensor


ENVIROMUX-LDSx-y
  • For detecting water presence and warning of flooding.
  • Detects liquid depth >0.1" (2.5 mm).
  • Minimum puddle: 0.6" (15 mm) diameter.
  • 100% waterproof electronics.
  • Detects any liquid or moisture, except deionized water.
  • Voltage and current:
    • Open Circuit: 5VDC max @ 1µA.
    • Closed circuit: <300mV @ 10.7mA.
  • RJ45 connector.
  • Voltage Supply: 12VDC
  • Current Consumption: 20mA
  • Supports CAT5/5e/6 cable up to 1,000 ft. (305 m)
  • Available water sensor cable (x) lengths: 1/10/50/100/200/400/600/800/1000 feet.
    • Bend radius: 0.375" (9.53 mm)
  • Plenum rating: CL2P (UL)
  • Available 2-wire cable (y) lengths: 5/10/20/50/100 feet.
    • Contact an NTI product consultant for cable lengths over 100 feet (30 meters) - supports up to 1,000 feet (305 meters).
  • Powered by ENVIROMUX-SEMS-16U and SERIMUX-S-x.
  • Regulatory approvals: CE, RoHS
  • Requires the ENVIROMUX-SEMS-16U and SERIMUX-S-x to operate.
  • Use self-adhesive clips (ENVIROMUX-CLPxx-LD) to prevent sensor rope cable from shifing after installation


Legacy Chemical Detection Sensor


ENVIROMUX-CDSx-y
  • For detecting the presence of chemical liquid.
    • Reliably senses acids, bases, and other conductive liquids.
  • Detects liquid depth >0.1" (2.5 mm).
  • Minimum puddle: 0.6" (15 mm) diameter.
  • Chemical resistant – cable functions normally after seven-day exposure to:
    • Fresh deionized water o Tap water o Sulfuric acid (98%)
    • Sulfuric acid (50%)
    • Hydrochloric acid (37%)
    • Sodium hydroxide (10%)
    • Aqua regia
    • Ethylene glycol (60% in DI water)
  • Voltage and current:
    • Open Circuit: 5VDC max @ 1µA.
    • Closed circuit: <300mV @ 10.7mA.
  • RJ45 connector.
  • Supports CAT5/5e/6 cable up to 1,000 ft. (305 m)
  • Available chemical sensor cable (x) lengths: 1/10/50/100 feet.
    • 100% waterproof
  • Available 2-wire cable (y) lengths: 5/10/20/50/100 feet.
    • Contact an NTI product consultant for cable lengths over 100 feet (30 meters) – supports up to 1,000 feet (305 meters).
    • Powered by ENVIROMUX-SEMS-16U or SERIMUX-S-x.
    • Requires the ENVIROMUX-SEMS-16U or SERIMUX-S-x to operate.
  • Use self-adhesive clips (ENVIROMUX-CLPxx-LD) to prevent sensor rope cable from shifing after installation


Self-Adhesive Clips for Liquid/Chemical Sensor Rope


ENVIROMUX-CLPxx-LD
  • Use to prevent sensor rope cable from shifting after installation
  • Self-adhesive backing for easy installation
  • Recommended distance between clips
    • Cables less than 5 ft long: one clip at each end.
    • Cables more than 5 ft long: minimum 5 ft apart.
  • Material: Nylon
  • Available quantities per package: 10, 100
  • Compatible with ENVIROMUX-LDSx-y, ENVIROMUX-CDSx-y, ENVIROMUX-LDx-y and ENVIROMUX-CDx-y